How to effectively implement a rapid and reasonable safety evacuation system in hospitals
2022-07-28 11:40:00 【Ankerui Huanan】
Encore Hua Nan
【 Abstract 】: The fire emergency lighting and evacuation indication system is controlled by the controller 、 Centralized power supply and lamps ( Evacuation indicating lamps 、 Emergency lighting fixtures ) Wait for several parts to make up . System USES Windonws7 System , It can support linkage alarm 、 System monitoring 、 Fault alarm 、 Self inspection 、 Standby power 、 Record storage and query 、 Guide optical flow 、 Authority control and other functions , With centralized control 、 High flexibility and reliability . Cooperate with various installation methods 、 Signs and lights with various degrees of protection , It is suitable for high building density in the building area 、 Many divisions 、 There are many internal fire compartments 、 Hospital projects with complex lamp circuits .
【 key word 】: Centralized power supply ; Centralized control ; Fire emergency lighting and evacuation indication system ; The hospital
0 . Preface
With the economy 、 The rapid development of science and technology , People began to pursue the humanization of architectural facilities 、 Rationalization , A large number of high-rise super large buildings , And the emergence of underground buildings has led to longer building passages 、 More complicated . With the improvement of people's safety awareness , Based on people-oriented 、 The idea of putting life safety first , For people intensive 、 Long evacuation distance 、 There are many evacuation routes 、 Many turns 、 Buildings with complex environment , The traditional evacuation mode cannot be used for timely maintenance of lamps , When the fire broke out , There is no reasonable guidance for personnel evacuation and escape , Therefore, implement a rapid and reasonable safety evacuation system , Guiding personnel to escape in time is an important measure to avoid causing mass casualties , In this way, centralized emergency lighting and evacuation indication system came into being .
The centralized emergency lighting and evacuation indication system can accurately realize the real-time monitoring and control of all emergency lamps 、 daily 24 Hourly management and maintenance , Ensure the normal operation of the system , Safety in case of fire 、 accuracy 、 Quickly guide personnel to the safe area , Reduce casualties .
1. Industry Introduction
1.1 Industry background
The medical industry is an industry closely related to the life and health of residents , Modern hospital buildings tend to be high-rise 、 Large scale and complexity , It is the complex functions used in all buildings 、 One of the buildings with high safety requirements . Hospitals belong to social public service places , Vulnerable groups of patients are concentrated 、 There's a lot of traffic , The connection of passages in the building is complex , Bedding 、 paper 、 There are many inflammables such as chemicals . There are many kinds of medical equipment in the hospital, and the power load is large , Social medical institutions are developing rapidly , Help people get out sick , However, many potential safety hazards cannot be ignored , In case of fire , It will cause huge property losses and casualties .
1.2 Industry standard
Ø 《 Technical specification for fire emergency lighting and evacuation indication system 》GB51309-2018
Ø 《 Fire emergency lighting and evacuation indication system 》GB17945-2010
Ø 《 Code for fire protection design of buildings 》GB50016-2014
Ø 《 Technical code for construction of hospital clean operation Department 》GB50333-2013
Ø 《 Code for electrical design of medical buildings 》JGJ312-2013
Ø 《 Code for architectural design of general hospital 》GB51039-2014
1.3 Regional division and regional characteristics
According to the demand of different areas in the hospital building for emergency lighting and evacuation instructions, it can be divided into three areas , For example, the architectural division of a hospital :
1. Conventional areas : Such as the office building in the hospital 、 Living quarters 、 Inpatient building, etc , There is no special need for emergency evacuation lamps in the area .
2. Personnel flow area : This area is generally registered 、 Payment hall , There is a large flow of people in the area , The place is empty , Personnel are unfamiliar with the building structure , High dependence on evacuation indication system during evacuation .
3. Clean area : There is a certain cleaning demand for the equipment in this area , Such as the clean passage in the operation Department .

2. Project introduction
2.1 Project brief introduction
This project is a hospital project , With internal medicine 、 Surgery 、 Orthopedics and traumatology 、 Anorectal 、 Department of gynaecology 、 Pediatrics and other departments , It is divided into emergency building 、 Outpatient building, inpatient building and other buildings . Our company is responsible for the inpatient building of emergency medicine in the second phase project of the hospital , Including its underground buildings , Most of them are conventional areas and personnel flow areas . Fire emergency evacuation indication system is required for emergency evacuation signs in all places , When a fire or emergency occurs , The specific fire location can be detected through the smoke detector of the fire monitoring system , And transmit the command to the fire host of the system by means of communication , Point to... With the arrow of the evacuation sign in the control place , Ensure that personnel escape and evacuate in the right direction .
2.2 Project difficulties 、 Special point
Ø The building density in the hospital building area is high 、 Many divisions , There are many internal fire compartments , The circuit of lamps is complex , How to arrange the fire emergency lighting and evacuation indication system
Ø In case of an emergency, the evacuation speed of patients in the inpatient building is slower than that in other places , Some patients with special conditions also need a stretcher or help to leave slowly , For evacuation lighting in this area , Determination of emergency time
2.3 Project selection
2.3.1 Emergency lighting controller

2.3.2 Centralized power supply for emergency lighting

2.3.3 Lamps and lanterns

2.4 System networking diagram

2.5 System diagram of site part

Five floors underground a District power distribution plan

Sixth floor local power distribution plan

Local intelligent evacuation lighting on the fifth floor , Communication plan of distribution box
2.6 Field application photos




3. Introduction to system scheme
3.1 Scheme topology

Combined with the inpatient building project of our hospital , The inpatient building includes conventional area and personnel flow area , Usually the first floor is the registration and toll area , The flow of people is large , The requirements for evacuation signs are mostly in case of emergency , It can be clearly seen in the chaos of the scene . Other floors are inpatient wards of different departments , The staff are mostly medical staff 、 disease 、 Caregivers , Consider the patient's ability to move , Appropriately extend the emergency time of lamps . There are staircases and less open areas in the inpatient building , Consider the need for energy conservation , Properly install induction lamps .
3.2 System software operation interface and function
Main interface of system operation

Contains toolbars 、 Graphic display 、 Layer list 、 status bar , You can intuitively view the operation status of the monitoring equipment , And switch directly to the specific fault bit according to the actual content of the status bar .
Lamp configuration interface

You can view the status and quantity of all lamps
Event recording interface

You can view historical operations 、 Fault information , You can query by date
3.3 Regional product use demand

3.4 System composition
The fire emergency lighting and evacuation indication system is controlled by the controller ( host )、 Centralized power supply / Distribution box and lamps ( Evacuation indicating lamps 、 Emergency lighting fixtures ) Wait for several parts to make up .

The controller is the host of the fire emergency lighting and evacuation indication system . The controller monitors each terminal in real time through the bus network , It can report the fault of each equipment and lamp in real time . In case of danger , Automatically issue information instructions to each terminal , The terminal starts working after receiving the instruction , Such as stroboscopic 、 open 、 Turn off the lights, etc , Real time indication of safe evacuation routes .
Centralized power supply is a standby centralized emergency power supply device installed in the building . When a building fires 、 In case of accident or other emergency , The emergency power supply can be the fire sign lamp 、 Emergency power supply shall be provided for lighting lamps , Ensure the normal operation of fire emergency lighting and evacuation instructions .
The distribution box is a power supply device installed in the building . When a building fires 、 In case of accident or other emergency , The distribution box can be a fire sign lamp 、 Lighting power supply , Ensure the normal operation of fire emergency lighting and evacuation indication system .
Emergency lighting fixtures provide lighting for personnel evacuation . The installation method is wall mounted 、 Ceiling type 、 Embedded type .
The evacuation indicator lamp guides the direction of personnel evacuation , To the left 、 Right and two-way sign lamps are generally used to indicate the direction of evacuation , Directional sign lamps are generally used to indicate emergency exits 、 Floors and shelters . The installation method is wall mounted 、 Hanging type 、 Buried .
4. Conclusion
With the rapid development of China's economy , Progress in science and technology , The importance of building intelligence and building fire protection has also increased , This paper briefly introduces the hospital industry and our company's fire emergency evacuation indication system scheme in the hospital industry , Combined with the completed project, the application of the scheme in the actual project is analyzed , It fully shows the simplicity in the networking of such projects 、 flexible 、 Stable 、 Low cost advantage . The fire emergency evacuation indication system can solve the problem that the traditional fire emergency evacuation indication system has no centralized control 、 The indication direction is fixed 、 The evacuation route cannot be changed 、 The indication effect is not ideal 、 Low safety performance .
Ankerui electric focuses on building products of various fire security systems , On the premise of meeting the requirements of national industrial standards , Provide intelligent services for all kinds of buildings 、 reasonable 、 Energy saving 、 Cheap fire-fighting solutions and products , For fire prevention and disaster reduction 、 Make a contribution to ensuring the safety of people's lives and property !
reference
[1]. Product selection manual of ankerui Electric Co., Ltd .2018.01
[2].GB50116-2014 Code for fire protection design of buildings [S].
[3].GB17945-2010《 Fire emergency lighting and evacuation indication system 》[S].
[4].GB51309-2018《 Technical standard for fire emergency lighting and evacuation indication system 》[S].
边栏推荐
- Advanced database technology learning notes 1 -- Oracle deployment and pl/sql overview
- Localization, low latency, green and low carbon: Alibaba cloud officially launched Fuzhou data center
- Flutter教程之带有 GoRouter 的 Flutter Navigator 2.0,使用 go_router 包了解 Flutter 中的声明式路由机制(教程含源码)
- STM32 drives st7701s chip (V ⅰ V0 mobile phone screen change price)
- Full version of H5 social chat platform source code [complete database + complete document tutorial]
- Rongyun IM & RTC capabilities on new sites
- What kind of knowledge payment system functions are more conducive to the development of the platform and lecturers?
- How to deal with invalid objects monitored by Oracle every day in the production environment?
- Who's the big God help? Let's see how Oracle number type parsing works. Struct{scale=15, Val
- MySQL离线同步到odps的时候 可以配置动态分区吗
猜你喜欢

Good use explosion! The idea version of postman has been released, and its functions are really powerful
![[geek challenge 2019] babysql-1 | SQL injection](/img/21/b5b4727178a585e610d743e92248f7.png)
[geek challenge 2019] babysql-1 | SQL injection

Three methods of using unity mouse to drive objects

Sirius network verification source code / official genuine / included building tutorial

Localization, low latency, green and low carbon: Alibaba cloud officially launched Fuzhou data center

The fifth generation verification code of "cloud centered, insensitive and extremely fast" is coming heavily

outlook突然变得很慢很卡怎么解决

什么是WordPress

什么是WordPress
![Two point, three point, 01 point plan [bullet I]](/img/12/5cc55b5f4f0bbcd5b89a9601eed824.png)
Two point, three point, 01 point plan [bullet I]
随机推荐
【MySQL】Got an error reading communication packets
Who's the big God help? Let's see how Oracle number type parsing works. Struct{scale=15, Val
【C语言】的%*d、%.*s等详解:「建议收藏」
vim命令下显示行号[通俗易懂]
哪位大神帮看下 oracle number类型解析 怎么搞 Struct{scale=15,val
用c语言编写学生成绩管理系统(c语言学生成绩管理系统删除)
Thinkphp5 behavior hook return result (data) example
CVPR2021 行人重识别/Person Re-identification 论文+开源代码汇总
服务器在线测速系统源码
Localization, low latency, green and low carbon: Alibaba cloud officially launched Fuzhou data center
Database advanced learning notes -- object type
保障邮箱安全,验证码四个优势
Display line number under VIM command [easy to understand]
五面阿里技术专家岗,已拿offer,这些面试题你能答出多少
ripro9.0修正升级版+WP两款美化包+稀有插件
No swagger, what do I use?
Summary of common RSA related problems in CTF: basic RSA encryption and decryption
Zotero document manager and its use posture (updated from time to time)
小水滴2.0网站导航网模板
Two point, three point, 01 point plan [bullet I]