The 100% question bank provides Fire service operators Examination questions 、 Fire service operators Test prediction questions 、 Fire service operators The real exam question 、 Fire service operators Certificate examination question bank, etc , Provide online questions and brush questions , Online mock exam , Help you pass the exam easily .

23、 Fixed fire monitor main fire extinguishing system 、 The switching function acceptance requirements of standby power supply include :( )
A、 System master 、 The standby power supply is on , Cut off the main power supply , The standby power supply shall be able to be put into operation automatically
B、 Restore the main power supply , The main power supply shall be able to be put into operation automatically
C、 Power on the control unit , And make the control device of fire pump set in automatic state
D、 Manually start a fire pump set , Observe whether the fire pump set and related equipment operate normally
answer :A-B
analysis : Fixed fire monitor main fire extinguishing system 、 Acceptance requirements for switching function of standby power supply : System master 、 The standby power supply is on , Cut off the main power supply , The standby power supply shall be able to be put into operation automatically ; Restore the main power supply , The main power supply shall be able to be put into operation automatically .
24、 Which of the following meets the functional acceptance requirements of the fire pump set of the fixed fire monitor fire extinguishing system :( )
A、 According to the system design requirements , Start the fire pump set , Observe whether the fire pump set and related equipment operate normally , If normal , The fire pump set is under the design load , Continuous operation shall not be less than 2h.
B、 Power on the control unit , And make the control device of fire pump set in automatic state , Manually start a fire pump set , Observe whether the fire pump set and related equipment operate normally
C、 Simulate anti pump unit failure , Stop the pump , here , The standby fire pump set shall be able to put into operation automatically
D、 The fire pump set is under the design load , Continuous operation shall not be less than 2h
answer :A-B-C
analysis : Requirements for functional acceptance of fire pump set of fixed fire monitor fire extinguishing system :1) The operation acceptance requirements of fire pump unit shall be in accordance with the system design requirements , Start the fire pump set , Observe whether the fire pump set and related equipment operate normally , If normal , The fire pump set is under the design load , Continuous operation shall not be less than 2h.2) Fixed fire monitor is mainly used for fire extinguishing system 、 Acceptance requirements for automatic switching function of standby pump set : Power on the control unit , And make the control device of fire pump set in automatic state , Manually start a fire pump set , Observe whether the fire pump set and related equipment operate normally , If normal , Then simulate the failure of anti pump unit in the control device of fire pump unit , Stop the pump . here , The standby fire pump set shall be able to put into operation automatically . The fire pump set is under the design load , Continuous operation shall not be less than 30min.
25、 What meets the acceptance requirements for the linkage control function of the fixed fire monitor fire extinguishing system is :( )
A、 Spot check the designed linkage control unit
B、 Power on the system , Make the controlled equipment of the linkage control unit to be inspected in automatic state , Press the corresponding linkage start button , The unit shall be able to automatically start the fire pump set according to the design requirements
C、 Open valves and other related equipment , Until the fire monitor sprays extinguishing agent ( Or water curtain protection system )
D、 The action and signal feedback of the unit equipment shall meet the design requirements
answer :B-C-D
analysis : Acceptance requirements for linkage control function of fixed fire monitor fire extinguishing system : Check one by one according to the designed linkage control unit . Power on the system , Make the controlled equipment of the linkage control unit to be inspected in automatic state , Press the corresponding linkage start button , The unit shall be able to automatically start the fire pump set according to the design requirements , Open valves and other related equipment , Until the fire monitor sprays extinguishing agent ( Or water curtain protection system ). The action and signal feedback of the unit equipment shall meet the design requirements .

26、 The following items that meet the requirements of the acceptance test conditions for the injection function of the fixed fire monitor fire extinguishing system are ( ):
A、 The water monitor and water curtain protection system use fire water for spraying
B、 The proportional mixing device of foam monitor system and the specification of foam liquid shall meet the design requirements
C、 The water supply of the fire pump unit reaches the design water supply pressure
D、 Dry powder model of dry powder gun system 、 specifications 、 Reserves and specifications of nitrogen cylinder group 、 The pressure shall meet the system design requirements
answer :A-B-D
analysis : Requirements for acceptance test conditions of injection function of fixed fire monitor fire extinguishing system :1) The water monitor and water curtain protection system use fire water for spraying .2) The proportional mixing device of foam monitor system and the specification of foam liquid shall meet the design requirements .3) The water supply of the fire pump unit reaches the rated water supply pressure .4) Dry powder model of dry powder gun system 、 specifications 、 Reserves and specifications of nitrogen cylinder group 、 The pressure shall meet the system design requirements .5) The manual startup and linkage control functions of the system are normal .6) The valves involved in the control in the system work normally .
27、 The following items that meet the requirements of the acceptance test conditions for the injection function of the fixed fire monitor fire extinguishing system are ( ):
A、 The manual startup and linkage control functions of the system are normal
B、 The valves involved in the control in the system work normally
C、 The water monitor and water curtain protection system use barreled water for spraying
D、 Dry powder model of dry powder gun system 、 specifications 、 Reserves and specifications of nitrogen cylinder group 、 The pressure shall meet the system design requirements
answer :A-B-D
analysis : Requirements for acceptance test conditions of injection function of fixed fire monitor fire extinguishing system :1) The water monitor and water curtain protection system use fire water for spraying .2) The proportional mixing device of foam monitor system and the specification of foam liquid shall meet the design requirements .3) The water supply of the fire pump unit reaches the rated water supply pressure .4) Dry powder model of dry powder gun system 、 specifications 、 Reserves and specifications of nitrogen cylinder group 、 The pressure shall meet the system design requirements .5) The manual startup and linkage control functions of the system are normal .6) The valves involved in the control in the system work normally .
28、 There are :( )
A、 water cannon 、 Water curtain 、 The actual working pressure of the foam gun shall not be less than the corresponding design working pressure .
B、 water cannon 、 Foam cannon 、 The level of dry powder cannon 、 The pitch return angle shall meet the design requirements , The spray angle of the fire water monitor with DC spray conversion function shall meet the design requirements
C、 The spray angle of the protective water curtain nozzle shall meet the design requirements
D、 Foam ratio of foam gun system 、 The mixing ratio of the mixed liquid provided by the mixing device shall meet the design requirements
answer :A-B-D
analysis : Requirements for the results of the spray function test of the fixed fire monitor fire extinguishing system :1) water cannon 、 Water curtain 、 The actual working pressure of the foam gun shall not be less than the corresponding design working pressure .2) water cannon 、 Foam cannon 、 The level of dry powder cannon 、 The pitch return angle shall meet the design requirements , The spray angle of the fire water monitor with DC spray conversion function shall meet the design requirements .3) The spray height of the protective water curtain nozzle shall meet the design requirements .4) Foam ratio of foam gun system 、 The mixing ratio of the mixed liquid provided by the mixing device shall meet the design requirements .5) The time from the start of water monitor system and foam monitor system to the ejection of water or foam shall not be greater than 5min, The time from the start-up of the dry powder gun system to the ejection of dry powder shall not be greater than 2min.
29、 There are :( )
A、 The time from the start-up of the dry powder gun system to the ejection of dry powder shall not be greater than 5min.
B、 water cannon 、 Foam cannon 、 The level of dry powder cannon 、 The pitch return angle shall meet the design requirements , The spray angle of the fire water monitor with DC spray conversion function shall meet the design requirements
C、 The time from the start of water monitor system and foam monitor system to the ejection of water or foam shall not be greater than 5min
D、 Foam ratio of foam gun system 、 The mixing ratio of the mixed liquid provided by the mixing device shall meet the design requirements
answer :B-C-D
analysis : Requirements for the results of the spray function test of the fixed fire monitor fire extinguishing system :1) water cannon 、 Water curtain 、 The actual working pressure of the foam gun shall not be less than the corresponding design working pressure .2) water cannon 、 Foam cannon 、 The level of dry powder cannon 、 The pitch return angle shall meet the design requirements , The spray angle of the fire water monitor with DC spray conversion function shall meet the design requirements .3) The spray height of the protective water curtain nozzle shall meet the design requirements .4) Foam ratio of foam gun system 、 The mixing ratio of the mixed liquid provided by the mixing device shall meet the design requirements .5) The time from the start of water monitor system and foam monitor system to the ejection of water or foam shall not be greater than 5min, The time from the start-up of the dry powder gun system to the ejection of dry powder shall not be greater than 2min.
边栏推荐
- Introduction to Chinese text error correction task
- 秋招-准备计划
- 如何查看Pod里容器名称
- Interview questions for software testing is a collection of interview questions for senior test engineers, which is exclusive to the whole network
- 项目版本号怎么命名?看起来牛B
- 某公司给每个工位装监控:只为看员工写代码?
- Hack the box - Introduction to networking module detailed Chinese tutorial
- Hack The Box - Introduction to Networking Module详细讲解中文教程
- Select sort / insert sort / bubble sort
- MBA-day29 算术-绝对值初步认识
猜你喜欢

Redis持久化-RDB

Efficient, reliable and safe open source solution for serial communication

ES Cluster in Red status: what about write & delete operations?

FTP experiment and overview

这种项目,最好别接!

Attack and defense world -- easy_ web

The idea YML file code does not prompt the solution
![[personal summary] end of July 24, 2022](/img/9e/dfc37c2684aa8849291817782c947b.png)
[personal summary] end of July 24, 2022

调试利器!一款轻量级日志库 log.c

芯片的翻新和造假,人被坑麻了
随机推荐
这种项目,最好别接!
[personal summary] end of July 24, 2022
No EGL display error resolution
Redis事务
Redis persistence AOF
Redis持久化-RDB
It's enough for newcomers to learn how to do functional tests
[cloud native] introduction and use of feign of microservices
The refurbishment and counterfeiting of chips have made people feel numb
Redis master-slave replication
The idea YML file code does not prompt the solution
Hack the box -sql injection fundamentals module detailed Chinese tutorial
leetcode-Array
How to name the project version number? Looks like cow b
idea yml 文件代码不提示解决方案
Kingbasees SQL language reference manual of Jincang database (9. Common DDL clauses)
SSH Remote Management
Redis persistence RDB
Redis发布订阅
Redis 官方可视化工具,高颜值,功能真心强大!