当前位置:网站首页>Grounding relay dd-1/60
Grounding relay dd-1/60
2022-07-04 05:42:00 【Comprehensive operation of Shanghai Joseph Electric Appliance C】
Series models
DD-1/40 Grounding relay ;
DD-1/50 Grounding relay ;
DD-1/60 Grounding relay ;
One 、 purpose
DD-1 Type a grounding relay is an overcurrent relay with instantaneous action , It is used as grounding zero sequence overcurrent protection for high-voltage three-phase alternator and motor in small current grounded power system . The relay coil is connected to the zero sequence current transformer ( Cable type 、 Busbar type ) Or zero sequence current protection composed of three phase current transformers . When the zero point of the protected motor is grounded through impedance, the relay is connected to the differential circuit of the converter . When the relay is connected to the zero sequence current filter composed of three current transformers , Locking relay shall also be connected , To prevent possible maloperation caused by unstable current due to external through short circuit .
Two 、 Main technical parameters
Setting range of relay action current and coil impedance value .
Relays of various specifications , When the coils are connected in series or in parallel , Its impedance angle is +35°.
Rated current :100mA、 frequency 50Hz.
Set the scale error : No more than ±6%.
Action value becomes worse : No more than 6%.
Return coefficient : Not less than 0.5.
Power consumption : When the setting current is small, it shall not be greater than 0.015VA.
Action time : stay 1.2 When times the setting current , The action time shall not be greater than 0.3s;3 When times the setting current , The action time shall not be greater than 0.1s.
Contact capacity : The voltage is not greater than 250V, The current is not greater than 0.5A when , The breaking capacity of relay contact is in DC inductive load circuit ( The intermediate constant is 5±0.75ms) by 20W,
In the AC circuit 100VA.
Medium strength : The insulation between the relay circuit and the enclosure metal shall withstand AC 50Hz, voltage 2000V after 1min Without breakdown or flashover .
3、 ... and 、 Internal wiring diagram and external wiring diagram
Ordering instructions :
The relay model and specification must be indicated when ordering 、 Power supply mode and setting range of auxiliary power supply 、 Structural form code 、 Wiring mode before or after the board 、 Quantity and other requirements .
“ The coil of grounding relay is connected to zero sequence current transformer ( Cable type 、 Busbar type 、 Or a zero sequence current filter composed of three phase current transformers ). When the zero point of the protected motor is grounded through impedance, the relay is connected to the differential circuit of the converter . When the relay is connected to the zero sequence current filter composed of three current transformers , Locking relay shall also be connected , To prevent possible maloperation caused by unstable current due to external through short circuit .”
Shanghai Joseph relay business department
边栏推荐
- 力扣(LeetCode)184. 部门工资最高的员工(2022.07.03)
- What is MQ?
- 云原生架构实战案例及优化解决方案
- BeanFactoryPostProcessor 与 BeanPostProcessor 相关子类概述
- Recommended system 1 --- framework
- Design and implementation of tcp/ip series overview
- (4) Canal multi instance use
- left_and_right_net可解释性设计
- Graduation design of small programs -- small programs of food and recipes
- 724. 寻找数组的中心下标
猜你喜欢
云原生架构实战案例及优化解决方案
Overview of relevant subclasses of beanfactorypostprocessor and beanpostprocessor
Kubernets first meeting
19.Frambuffer应用编程
拓扑排序和关键路径的图形化显示
Just do it with your hands 7 - * project construction details 2 - hook configuration
LM小型可编程控制器软件(基于CoDeSys)笔记二十二:错误4268/4052
Enterprise level log analysis system elk (if things backfire, there must be other arrangements)
Analysis of classical pointer and array written test questions in C language
Canoe panel learning video
随机推荐
px em rem的区别
With the advent of the IP era, how can E-sports hotels take advantage of the "east wind" of games?
ETCD数据库源码分析——初始化总览
left_and_right_net可解释性设计
Penetration tool - sqlmap
Recommended system 1 --- framework
Arc135 C (the proof is not very clear)
BUU-Crypto-Cipher
Ping port artifact psping
Unity2d -- character moves and turns
LC周赛300
JS扁平化数形结构的数组
2022 question bank and answers for safety management personnel of hazardous chemical business units
Unity2D--人物移动并转身
Upper computer software development - log information is stored in the database based on log4net
How much computing power does transformer have
Tutle clock improved version
每周小结(*63):关于正能量
拓扑排序和关键路径的图形化显示
配置交叉编译工具链和环境变量