Design and analysis of contactor coil control circuit
2022-07-28 06:24:00 【Tsd-Xu】
As a typical device of small current control and large current, contactor is widely used in the field of automation design and intelligent control , Here is a brief introduction to my understanding of contactor control circuit .
1. Typical control circuit 
2. working principle
K1 For contactor ,D1 Schottky diode ,Q1 by mos tube , When the control signal RELAY For high voltage ,Q1 Conduction ,B The point is low , The coil generates magnetic force , Contactor pull . here IQ=200MA,ID=0MA.
When the control signal RELAY Low power level ,Q1 end ,B The point is high level and will cause B The point voltage is greater than 24.55V, be D1 Conduction B The point is clamped at 24.55V, Not quite right MOS Tube damage .ID=200MA, Formation of current storage , When ID Less than 80MA The contactor is disconnected .
3. Disconnection time analysis
The above circuits have no problem in common application scenarios , But when there is a requirement for the breaking time of the contactor , May not meet the requirements , The following analysis .
about K1:
------------------------------①
be △ID=200-80=120MA, Voltage across the inductor U=0.55V, The measured equivalent inductance of the coil is 35mh, be △t≈8MS. Plus the inherent breaking time of the contactor 10-15ms, Then the total disconnection time will be greater than 20ms, Unacceptable in many application scenarios .
4. Rectification direction
from ① Type it , If you want to reduce △t, Can pass , Reduce L and △ID, increase U, because L and △ID It is the inherent property of contactor , You cannot change , Therefore, our adjustable means are only limited to increasing the voltage at both ends of the coil when it is turned off .
1: Available in diode D1 Series resistance , Increase the voltage .
2: A slightly higher threshold can be used TVS Tube as clamping device .
Note the following :
1,MOS Pipe selection needs to be improved VDS Breakdown voltage ;
2,LAYOUT when , Contactors need to be handled carefully ,MOS tube , Connection between diodes , Do not get too close to the signal line , Not too long , It will affect radiation emission, etc EMC experiment .
5. Experiment related waveforms 
chart 1 No diode, no TVS Disconnection time 
chart 2 There is reverse diode disconnection time 
chart 3 Add resistance to the diode
边栏推荐
- Agilent Agilent e5071 test impedance and attenuation are normal, except crosstalk ng--- Repair plan
- FLUKE福禄克Aircheck wifi测试仪无法配置文件?---终极解决心得
- Beta分布(概率的概率)
- 雷达成像 Matlab 仿真 4 —— 距离分辨率分析
- Perl入门学习(十一)文件操作
- arduino 读取模拟电压_MQ2气体/烟雾传感器如何工作及其与Arduino接口
- (PHP graduation project) obtained based on thinkphp5 campus news release management system
- Agilent安捷伦 E5071测试阻抗、衰减均正常,惟独串扰NG?---修复方案
- 天线效应解决办法
- PyTorch 学习笔记 2 —— About Tensor
猜你喜欢
随机推荐
PT physical aware based on multi voltage
Shuffle Net_v1-shuffle_v2
ICC2分析时序的神器 analyze_design_violations
EXFO 730c optical time domain reflectometer only has IOLm optical eye to upgrade OTDR (open OTDR permission)
【YOLOv5】环境搭建:Win11 + mx450
Install visual studio 2019 steps and vs2019 offline installation package on win7
Triode design, understanding saturation, linear region and cut-off region
(PHP graduation project) based on PHP user online submission management system
8类网线测试仪AEM testpro CV100 和FLUKE DSX-8000哪些事?
The short jumper dsx-8000 test is normal, but the dsx-5000 test has no length display?
ConNeXt
EXFO 730C光时域反射计只有iOLM光眼升级OTDR(开通otdr权限)
Distinguishing PCB quality by color is a joke in itself
PyTorch 学习笔记 1 —— Quick Start
Convert data in grilview into datatable
ICC2使用report_placement检查floorplan
AEM testpro K50 and south Guangdong survey
(PHP graduation project) based on thinkphp5 community property management system
(PHP graduation design) obtained based on PHP fruit sales store management system
Transformer 自注意力机制 及完整代码实现