当前位置:网站首页>Jogy-61 voltage relay
Jogy-61 voltage relay
2022-07-28 15:17:00 【Comprehensive operation of Shanghai Joseph Electric Appliance C】



brand : Shanghai Joseph
name : Static voltage relay
model :JOGY-61A1;JOGY-61B1
Rated voltage :48V,110V,220V/DC
Power consumption : No more than 2.5W
Series models
JOGY-60 Series guide rail static voltage relay ;JOGY-61A Rail static voltage relay ;
JOGY-61B Rail static voltage relay ;JOGY-62A Rail static voltage relay ;
JOGY-62B Rail static voltage relay ;JOGY-61A1 Rail static voltage relay ;
JOGY-61B1 Rail static voltage relay ;JOGY-621A Rail static voltage relay ;
JOGY-62B1 Rail static voltage relay ;
One 、 purpose
JOGY Series IC voltage relays are static AC voltage relays . For generator 、 Relay protection devices for transformers and transmission lines , As the action element of overvoltage protection and low voltage locking . The relay adopts digital dial switch , Switching regulated power supply , High performance intermediate relay , Ensure the safety and reliability of the whole machine .
This series of products is designed to replace DY Series of relays designed for upgrading products , The setting value is 15V The above do not need to add DC auxiliary power . The product also has high precision 、 Low power consumption 、 Fast action time 、 The return coefficient is high 、 The setting is intuitive and convenient 、 It has the advantages of wide setting range and no jitter when used as a low voltage . The overall dimension of the relay adopts guide rail installation, which can meet the special needs of customers .
Two 、 The meaning of the model
3、 ... and 、 Technical parameters
1. Voltage setting range
A) 01:1V ~140VAC
B) 02: 180V~500VAC ;
2. Rated auxiliary DC voltage : 48V、110V、220V.
3. Power consumption
a) AC loop power consumption : When the setting voltage is large , The power consumption of the relay is not greater than 2.5VA;
b) DC loop power consumption : Under rated auxiliary DC voltage , The relay power is not greater than 4W.
4. Allowable variation range of DC auxiliary voltage : 0.8-1.1 Times the rated value .
5. Action time
a) Overvoltage relay : from 0.8 The setting value of times rises to 1.2 When the setting value is doubled, the action time is not greater than 25ms.
b) Low voltage relay : from 2 times The setting value drops to 0.8 When the setting value is doubled, the action time is not greater than 25ms.
6. Return time
a) Overvoltage relay : from 1.2 The setting value is reduced to 0.8 Times the setting value , The return time shall not be greater than 25ms.
B) Undervoltage relay : from 0.8 times The setting value rises to 2 Times the setting value , The return time shall not be greater than 25ms.
7. Return coefficient :
A) The return coefficient of overvoltage relay shall not be less than 0.85.
B) The return coefficient of low voltage relay shall not be greater than 1.25.
8. Setting error : Under reference conditions , The voltage setting error is not greater than 5%.
9. Contact performance :
The voltage of relay contact is not greater than 250V, The current is not greater than 2A DC inductive load ( The time constant is 5ms±0.75ms) In circuit , The breaking capacity is 50W, When the voltage is not greater than 250V, The current is not greater than 1A In the AC circuit of ( The power factor is 0.4±0.1) The breaking capacity is 250VA.
10. Insulation resistance
Each circuit of the relay has no electrical connection with the exposed non live metal parts lian The insulation resistance between circuits of the system shall not be less than 300M2.
11. Medium strength
Between exposed non-metallic parts of each circuit pair of relay , And between the coil circuit and the contact circuit , Shall be able to withstand 2kV ( Valid values )、50Hz Of Current test voltage , after 1min test , There shall be no insulation breakdown or flashover .
12. Working conditions
a) No explosive medium is allowed in the place of use , The surrounding medium does not contain gases and conductive media that corrode and destroy metals , It is not allowed to be full of water vapor and serious mold ;
b) Strong vibration and impact are not allowed at the place of use ;
c) The place of use should be protected against rain 、 snow 、 wind 、 Sand equipment :
d) The place of use shall not exceed 1.5mT External magnetic induction intensity .
13. Electrical anti-interference relay shall conform to GB7261 and GB6261《 Electrical anti-interference test of static relay and protection device 》
Four 、 Internal wiring diagram
5、 ... and 、 Dimensions
JOGY-61 Voltage relay
Shanghai Joseph relay business department
Voltage relay is an electronic control device , It has a control system ( Also called input loop ) And the controlled system ( Also called output loop ), Usually used in automatic control circuit , It's actually a way of controlling a larger current with a smaller current “ Automatic switch ”. So in the circuit plays an automatic adjustment 、 safeguard 、 Switching circuit, etc . Mainly used for generator 、 Relay protection devices for transformers and transmission lines , As the starting element of overvoltage protection or low-voltage lockout .
Voltage relay is an input 、 A measuring relay whose characteristic quantity is voltage , It is divided into overvoltage relay and undervoltage relay . The former acts because the voltage value increases to the set value , Then it is in the dynamic state ; The latter acts because the voltage value decreases to the set value , Then it is released . Voltage relay has electromagnetic type 、 Transistor type .
边栏推荐
- The automatic prompt of vs code code is missing - a tick to solve it
- Instant experience | further improve application device compatibility with cts-d
- No files or folders found to process
- Three pain points of software development! How to solve the applet container?
- 一文看懂CRMEB开源在线教育知知识付费系统
- CCSP international registered cloud security experts set up examination rooms in China
- 使用cpolar发布树莓派网页(apache2网页的发布)
- [complete installation package & tutorial] sqlserver basic installation_ Sqlserver completely uninstalled_ Sqlserver custom installation_ Getting started with sqlserver_ SQLSERVER database
- crmeb pro2.2即将增加的功能都有哪些?
- Repvgg paper explanation and model reproduction using pytoch
猜你喜欢
随机推荐
3511. Water pouring problem
SystemVerilog
Compose learning notes 1-compose, state, flow, remember
crmeb标准版4.4都会增加哪些功能
iframe 标签
SystemVerilog
Shader顶点着色器修改顶点高度的一个思路
流畅到让人头皮发麻的单商户商城,你用过吗?
电压继电器DY-28C
Slider restore and validation (legal database)
crmeb 标准版Window+phpstudy8安装教程(一)
Idea2020.1.4 packages package collapse
SRTT-110VDC-4H-C时间继电器
代码比较干净的多商户商城系统
软件开发三大痛点!小程序容器如何解决?
安全与隐私计算在国内发展现状
@Solution to DS ('slave') multi data source compatible transaction problem
Stack expression
Instructions for common symbols in kotlin
为什么企业需要用户自治的数字身 份