Specific method example of V20 frequency converter manual automatic switching (local remote switching)

2022-07-07 23:12:00 AAA_ Automation Engineer

V20 The frequency converter switches manually and automatically ( Local remote switching ) Examples of specific methods

0.1
0.2
A commonly used typical design is to control the start and stop of the frequency converter through the button of the electrical cabinet in the local mode , Adjust the frequency through the frequency converter panel ; Through... In remote mode PLC Of DO The output controls the start and stop of the frequency converter , In both modes, it passes through the inverter AO Output frequency feedback , Output operation feedback through intermediate relay .

Siemens V20 The converter has no macro in this mode , You need to set up your own , Specific methods can be referred to as follows :

The design wiring mode is as follows
DI1: start-up / Stop control input
DI2: long-range / Local switching input
DO1: Operational feedback
DO2: Fault feedback
AI2: Remote frequency setting (4~20mA)
AO1: Frequency feedback (4~20mA)

The circuit diagram is as follows ,

3
The control requirements are as follows
Local control :DI1 Control the start and stop of frequency conversion ,BOP Panel given frequency
far