2022 Heilongjiang latest fire protection facility operator simulation test question bank and answers
2022-07-01 17:46:00 【100% question bank】
The 100% question bank provides Firefighter facility operator Examination questions 、 Firefighter facility operator Test prediction questions 、 Firefighter facility operator The real exam question 、 Firefighter facility operator Certificate examination question bank, etc , Provide online questions and brush questions , Online mock exam , Help you pass the exam easily .

276、 The fire control room is equipped with a dedicated telephone switchboard , Set up telephone extensions or telephone jacks on site .( )
answer : correct
analysis : Functions and use requirements of special fire telephone : The fire code has made clear provisions on the special telephone for fire protection : The fire control room is equipped with a dedicated telephone switchboard , Set up telephone extensions or telephone jacks on site . Direct call mode is adopted , No need to dial .
277、 The private telephone adopts the direct call method , No need to dial .( )
answer : correct
analysis : Functions and use requirements of special fire telephone : The fire code has made clear provisions on the special telephone for fire protection : The fire control room is equipped with a dedicated telephone switchboard , Set up telephone extensions or telephone jacks on site . Direct call mode is adopted , No need to dial .
278、 Evacuation indication sign refers to the sign used to indicate the safe evacuation of personnel in case of fire .( )
answer : correct
analysis : Emergency lighting and evacuation indication system : Fire emergency sign lamps and lanterns refer to fire emergency lamps and lanterns that use graphics and or words to explain relevant indication functions . Evacuation indication sign refers to the sign used to indicate the safe evacuation of personnel in case of fire .
279、 Fire emergency lighting after the normal power supply is cut off , The power conversion time shall meet :① Evacuation lighting ≤5s;② Backup lighting ≤5s( Financial and commercial trading venues ≤1.5s).( )
answer : correct
analysis : Requirements for the setting of emergency lighting fixtures :(1) Light source selection , Incandescent lamps are generally used 、 Fluorescent lamps, etc .(2) Fire emergency lighting after the normal power supply is cut off , The power conversion time shall meet :① Evacuation lighting ≤5s;② Backup lighting ≤5s( Financial and commercial trading venues ≤1.5s).(3) The emergency switching time of fire emergency lamps should be ≤5s; The emergency switching time of fire emergency lamps used in high-risk areas shall be ≤0.25s(4) Evacuation lighting should be on at ordinary times , However, the following exceptions can be made :①、 On holidays 、 When no one works or uses at night and only the on duty or security personnel are responsible for the management ;②、 When the emergency exit and evacuation direction can be identified by external light .(5) Dimmable safety exit sign lamps are used in the auditorium of cinemas .(6) Illumination requirements for fire emergency lighting fixtures ( A little ).(7) The emergency working time of fire emergency lamps shall not be less than 90min, And not less than the nominal emergency working time of the lamp itself .(8) Specifications and standards of fire emergency lamps ( A little ).(9) Selection scheme of specifications and forms of several types of building emergency lighting ( A little ).(10) The color of the sign lamp shall be green 、 Red 、 White combines with green 、 One of the four combinations of white and red .(11) Setting position of fire emergency lighting ( A little ).(12) Evacuation indicator light setting position ( A little ).
280、 The emergency switching time of fire emergency lamps should be ≤5s; The emergency switching time of fire emergency lamps used in high-risk areas shall be ≤0.25s.( )
answer : correct
analysis : Requirements for the setting of emergency lighting fixtures :(1) Light source selection , Incandescent lamps are generally used 、 Fluorescent lamps, etc .(2) Fire emergency lighting after the normal power supply is cut off , The power conversion time shall meet :① Evacuation lighting ≤5s;② Backup lighting ≤5s( Financial and commercial trading venues ≤1.5s).(3) The emergency switching time of fire emergency lamps should be ≤5s; The emergency switching time of fire emergency lamps used in high-risk areas shall be ≤0.25s(4) Evacuation lighting should be on at ordinary times , However, the following exceptions can be made :①、 On holidays 、 When no one works or uses at night and only the on duty or security personnel are responsible for the management ;②、 When the emergency exit and evacuation direction can be identified by external light .(5) Dimmable safety exit sign lamps are used in the auditorium of cinemas .(6) Illumination requirements for fire emergency lighting fixtures ( A little ).(7) The emergency working time of fire emergency lamps shall not be less than 90min, And not less than the nominal emergency working time of the lamp itself .(8) Specifications and standards of fire emergency lamps ( A little ).(9) Selection scheme of specifications and forms of several types of building emergency lighting ( A little ).(10) The color of the sign lamp shall be green 、 Red 、 White combines with green 、 One of the four combinations of white and red .(11) Setting position of fire emergency lighting ( A little ).(12) Evacuation indicator light setting position ( A little ).
281、 Evacuation lighting should be on at any time .( )
answer : error
analysis : Requirements for the setting of emergency lighting fixtures :(4) Evacuation lighting should be on at ordinary times , However, the following exceptions can be made :①、 On holidays 、 When no one works or uses at night and only the on duty or security personnel are responsible for the management ;②、 When the emergency exit and evacuation direction can be identified by external light .
282、 The electric light source used as an evacuation indicator requires a fast starting point 、 It is always on and easy to maintain , Usually choose incandescent lamp .( )
answer : correct
analysis : Requirements for the setting of emergency lighting fixtures :(1) Light source selection : The light source that can ignite quickly should be selected , Incandescent lamps are generally used 、 Fluorescent lamps, etc . When switching to realize emergency lighting under normal working lighting conditions , General fluorescent lamps can be selected . The electric light source used as an evacuation indicator requires a fast starting point 、 It is always on and easy to maintain , Usually choose incandescent lamp .
283、 Evacuation indicator light , It is generally located no more than... From the ground 1m On the wall , Never set it on the ceiling .( )
answer : correct
analysis : Requirements for the setting of emergency lighting fixtures :(12) Evacuation indicator light , It is generally located no more than... From the ground 1m On the wall . Never set it on the ceiling .
284、 Emergency lamps used , Do not let water enter the lamp body , If there is water, it should be removed in time . There is no need to cut off the power supply when clearing .( )
answer : error
analysis : Cleaning and maintenance of emergency lighting fixtures :(1) Appearance inspection and cleaning : The appearance shall be cleaned regularly 、 Check , Replace the damaged ones . When cleaning , Use a soft cloth dipped in soapy water to dry and wipe , Wipe it with a dry cloth .(2) Cut off the normal power supply according to the correct method , Use a stopwatch to measure the duration of the emergency working state .(3) Emergency lamps used , Do not let water enter the lamp body , If there is water, it should be removed in time . The power must be cut off when clearing .(4) The emergency lamps shall be tested regularly by professionals .(5) The battery shall have a certain service life .

285、 In order to use emergency lighting safely and effectively , The appearance shall be cleaned regularly 、 Check , Replace the damaged ones .( )
answer : correct
analysis : Cleaning and maintenance of emergency lighting fixtures :(1) Appearance inspection and cleaning : The appearance shall be cleaned regularly 、 Check , Replace the damaged ones . When cleaning , Use a soft cloth dipped in soapy water to dry and wipe , Wipe it with a dry cloth .(2) Cut off the normal power supply according to the correct method , Use a stopwatch to measure the duration of the emergency working state .(3) Emergency lamps used , Do not let water enter the lamp body , If there is water, it should be removed in time . The power must be cut off when clearing .(4) The emergency lamps shall be tested regularly by professionals .(5) The battery shall have a certain service life .
286、 Fire doors are divided into normally closed fire doors and normally open fire doors according to the opening and closing state .( )
answer : correct
analysis : Fire doors are divided into normally closed fire doors and normally open fire doors according to the opening and closing state .
287、 Normally open fire doors need to be closed manually in case of fire .( )
answer : error
analysis : Working principle of fire door :(1) Normally closed fire doors are usually closed under the action of door closers , Therefore, it can prevent the spread of fire and smoke in case of fire .(2) Normally open fire doors are usually open under the action of the releaser , In a fire , The releaser automatically releases , The fire door is closed under the action of door closer and sequencer , So as to play the due role of fire doors .(3) The working principle of normally open fire doors ( A little ).
288、 The fire door shall be a swing door opening in the direction of evacuation , It shall be able to be opened manually from either side after closing .( )
answer : correct
analysis : Functional requirements of fire doors :(1) The components are complete and intact , Flexible opening and closing 、 Close tightly .(2) The fire door shall be able to close automatically , Double fire doors shall be able to close in sequence .(3) The fire door shall be a swing door opening in the direction of evacuation , It shall be able to be opened manually from either side after closing .(4) Normally closed fire doors shall be able to close automatically after opening .(5) Electric normally open fire door , It shall automatically shut down and feed back the signal after the fire alarm .(6) Fire door set on the evacuation aisle and equipped with access control system , It shall be able to automatically and manually remove the access control system .
289、 Normally closed fire doors shall be able to close automatically after opening .( )
answer : correct
analysis : Functional requirements of fire doors :(1) The components are complete and intact , Flexible opening and closing 、 Close tightly .(2) The fire door shall be able to close automatically , Double fire doors shall be able to close in sequence .(3) The fire door shall be a swing door opening in the direction of evacuation , It shall be able to be opened manually from either side after closing .(4) Normally closed fire doors shall be able to close automatically after opening .(5) Electric normally open fire door , It shall automatically shut down and feed back the signal after the fire alarm .(6) Fire door set on the evacuation aisle and equipped with access control system , It shall be able to automatically and manually remove the access control system .
290、 Normally open fire doors are usually open under the action of fire door release , Close manually in case of fire .( )
answer : error
analysis : Working principle of fire door :(1) Normally closed fire doors are usually closed under the action of door closers , Therefore, it can prevent the spread of fire and smoke in case of fire .(2) Normally open fire doors are usually open under the action of the releaser , In a fire , The releaser automatically releases , The fire door is closed under the action of door closer and sequencer , So as to play the due role of fire doors .(3) The working principle of normally open fire doors ( A little ).
边栏推荐
- Research Report on development monitoring and investment prospects of China's smart environmental protection industry (2022 Edition)
- 《中国智慧环保产业发展监测与投资前景研究报告(2022版)》
- 中国超高分子量聚乙烯产业调研与投资前景报告(2022版)
- 目前炒期货在哪里开户最正规安全?怎么期货开户?
- SPIE Western optoelectronics exhibition returned offline and successfully held a science and engineering event
- Rotation order and universal lock of unity panel
- 整形数组合并【JS】
- Vulnhub range hacker_ Kid-v1.0.1
- 开发那些事儿:EasyCVR集群设备管理页面功能展示优化
- What are the six steps of the software development process? How to draw software development flow chart?
猜你喜欢

ISO 27001 Information Security Management System Certification

DNS

(16) ADC conversion experiment

多线程并发之CountDownLatch阻塞等待

Penetration practice vulnhub range Tornado

(28) Shape matching based on contour features

Replace UUID, nanoid is faster and safer!

【牛客网刷题系列 之 Verilog快速入门】~ 优先编码器电路①

Rotation order and universal lock of unity panel

ACM mm 2022 video understanding challenge video classification track champion autox team technology sharing
随机推荐
pyqt5中,在控件上画柱状图
SQL injection vulnerability (MySQL and MSSQL features)
多线程并发之CountDownLatch阻塞等待
[C language foundation] 12 strings
线上开通ETF基金账户安全吗?有哪些步骤?
中国超高分子量聚乙烯产业调研与投资前景报告(2022版)
[splishsplash] about how to receive / display user parameters, MVC mode and genparam on GUI and JSON
Good looking UI mall source code has been scanned, no back door, no encryption
String的trim()和substring()详解
The new server is packaged with the source code of H5 mall with an operation level value of several thousand
Encryption and decryption of tinyurl in leetcode
RadHat搭建内网YUM源服务器
Kia recalls some K3 new energy with potential safety hazards
In aks, use secret in CSI driver mount key vault
Iommu/smmuv3 code analysis (10) page table operation
JDBC:深入理解PreparedStatement和Statement[通俗易懂]
Length of learning and changing
Irradiance, Joule energy, exercise habits
Nielseniq found that 60% of the re launched products had poor returns
提交review时ReviewBoard出现500错误解决方法