Series models :
DJ-ZBS1 Two shift leakage ( The remaining ) Relay
DJ-ZBS2 Two shift leakage ( The remaining ) Relay
DJ-ZBS3 Two shift leakage ( The remaining ) Relay
DJ-ZBS The leakage relay was originally a split fixed installation , In order to meet the needs of current installation occasions , Shanghai Joseph relay factory in the original product DJ Product upgrade based on leakage relay , The development appears in the more popular separate guide rail installation DJ Leakage relay , It is widely used in coal mines and other places , It is also a coal mine leakage relay ; Small volume 、 Easy to install and use 、 Reliable movement 、 Continuous power supply is stable and easy to operate . Can adapt to users everywhere , It can be used to protect the line from ground fault , It is mainly used to prevent equipment accident or electrical fire caused by grounding fault current , It can also be used to provide indirect contact protection for the release of human electric shock .
One 、 Product overview
Integrated leakage relay ( Hereinafter referred to as relay ) Suitable for AC voltage to 660V Or higher TN、TT、 and IT System , The frequency is 50Hz. Detect the zero sequence current exceeding the setting value through the zero sequence current transformer ( The remaining ) Leakage current . The relay is connected with the circuit breaker of shunt release or voltage loss release 、 AC contactor 、 Magnetic starter and other components of leakage protection device , For leakage and electric shock protection , Can be equipped with buzzer 、 Signal and other acoustooptic devices are combined to form a leakage alarm device . Derive multiple models , Prefix such as HLJ、RLJ、ULJ Series and other models , It is actually a similar product . It plays a very important role in the power system , It is the basis to ensure the reliability of power supply .
Two 、 Product use
The leakage protection relay has small volume 、 Easy to install and use 、 Reliable movement 、 Continuous power supply is stable and easy to operate . Can adapt to users everywhere , It can be used to protect the line from ground fault , It is mainly used to prevent equipment accident or electrical fire caused by grounding fault current , It can also be used to provide indirect contact protection for the release of human electric shock .
The leakage relay can be connected with the circuit breaker with shunt release or voltage loss release 、 AC contactor 、 Magnetic starter and other components of leakage protection device , For leakage and electric shock protection , It can also be equipped with buzzer 、 Signal lamp and other acousto-optic devices are combined to form a leakage alarm device . With reset 、 instructions 、 Call the police 、 Reset and other functions .
It is not suitable for the central grounding point of power supply or direct grounding system 、 Low voltage distribution system . It is a new product of network reform for safe use . The action time of the relay is divided into fast type and delay type , When used together, the trunk line and branch line shall be protected by classification , It can completely replace the past LLJ-□F(S)、LLJ-□H(S)、JD1 And JD3 Series leakage relay .
3、 ... and 、 Product parameters
● Rating
Voltage rating : Rated voltage AC380V、AC660V、AC690V、AC1140V.
Working voltage value :DC24V、AC110V、AC127V、AC220V、AC380V. It can also be customized according to customer requirements .
Allowable variation range of power supply voltage : The voltage variation is the rated voltage 0.7 to 1.3 Times or wide power circuit .
Rated current value :16A、25A、32A、40A、63A、80A、100A、125A、200A、250A、320A、400A、630A、800A、1000A、1500A、1600A、2000A. Non standard point current can also be customized .
● Action value
Leakage action current : General or user-defined , Can also be 50-500mA Split gear or adjustable .
Leakage non action current : Half of the leakage action current .
Leakage action time : Delay type 0.2-2S.
Fast type ≤0.1S .
● Important parameter
The aperture of the transformer is round (L type ):M25、M45、M75、M100、M150、M160、M220.
Rectangular square ( Runway type ):45160、45220、45260、45320、45*450 etc. .
Output contact form : Open and close .
● Other parameters
Contact capacity : The output contact of the relay can be disconnected no more than 250V, The time constant is 5±0.75mS The DC inductive load circuit of is 50W; The voltage is not greater than 250V The AC circuit of is 50VA. The relay can be switched on for a long time 5A.
Power consumption : Not more than... Under rated voltage 5W.
ambient temperature :-10℃~+50℃.
Medium strength The conductive terminals of the relay are connected together between the exposed non live metal parts or shells , Able to bear 2000V( Valid values ) AC voltage , after 1 Minutes test without insulation breakdown or flashover .
Insulation resistance : The conductive terminals of the relay are connected together between the exposed non-metallic part and the shell , Use open circuit voltage 500V The insulation resistance measured by the megger of is not greater than 300MΩ.
Electrical life : The relay contact is connected to the circuit load of the specified capacity , The electric life is 100000 Time .
Four 、 working principle
The relay is an electronic current operated leakage relay , It is mainly composed of zero sequence current transformer 、 Electronic circuits 、 The working principle of the test circuit and outlet relay is as follows : The wiring is shown in the figure (1), Zero sequence transformer passing through the main line , When there is no leakage in the main line , The sum of vectors is equal to zero or minimal , When there is leakage or electric shock on the main line , The zero sequence transformer senses an unbalanced current vector and signal , When the circuit of zero sequence current transformer leaks to the ground iA+iB+iC≠0. Send it to the host for amplification , Check whether the leakage current exceeds the setting value , And send the results to the actuator for execution . At this time, the zero sequence current transformer will generate an induction signal , This signal is processed by electronic circuit , When the leakage current reaches the action value , Make the thyristor contact and make the relay act , Use relay normally open 、 The closing point controls the disconnection of the main circuit breaker or contactor , Cut off the fault line to achieve the purpose of protection . The test circuit is composed of resistors, buttons and other components , Press the test button , There is a current flowing through the transformer , Equivalent to the leakage current of the main line , The indicator light is on , The outlet relay should be able to act . Press the reset button , The light goes out , Outlet relay returns .
DJ-ZBS2 Leakage relay
1. Prevent electric shock accidents caused by leakage of electrical equipment and electrical lines ;
2. Prevent single-phase electric shock accidents during power use ;
3. Timely cut off the single-phase grounding electric shock fault in the operation of electrical equipment , Prevent fire accidents caused by electric leakage .
Shanghai Joseph relay business department
边栏推荐
- Longest non descent subsequence (LIS) (dynamic programming)
- Torch optimizer small parsing
- 漏电继电器LLJ-100FS
- Zhang Ping'an: accelerate cloud digital innovation and jointly build an industrial smart ecosystem
- What changes will PMP certification bring?
- y58.第三章 Kubernetes从入门到精通 -- 持续集成与部署(三一)
- Senior programmers must know and master. This article explains in detail the principle of MySQL master-slave synchronization, and recommends collecting
- 做自媒体,有哪些免费下载视频剪辑素材的网站?
- Knapsack problem unrelated to profit (depth first search)
- 一条 update 语句的生命经历
猜你喜欢
随机推荐
App clear data source code tracking
When deleting a file, the prompt "the length of the source file name is greater than the length supported by the system" cannot be deleted. Solution
2039: [蓝桥杯2022初赛] 李白打酒加强版 (动态规划)
《4》 Form
SQL injection cookie injection
Knapsack problem unrelated to profit (depth first search)
np. random. Shuffle and np Use swapaxis or transfer with caution
Batch size setting skills
qt 简单布局 盒子模型 加弹簧
ssm框架的简单案例
漏电继电器LLJ-100FS
论文阅读【Semantic Tag Augmented XlanV Model for Video Captioning】
背包问题(01背包,完全背包,动态规划)
设f(x)=∑x^n/n^2,证明f(x)+f(1-x)+lnxln(1-x)=∑1/n^2
Mybaits之多表查询(联合查询、嵌套查询)
Senior programmers must know and master. This article explains in detail the principle of MySQL master-slave synchronization, and recommends collecting
pytest测试框架——数据驱动
《5》 Table
MySQL数据库学习(7) -- pymysql简单介绍
【QT】自定义控件-Loading