Meet the level 3 requirements of ISO 2.0 with the level B construction standard of computer room | hybrid cloud infrastructure
2022-07-07 00:43:00 【New titanium cloud suit】
The new titanium cloud service has been accumulatively shared with you 658 Technical dry goods
《RightScale2021 Cloud status report 》 Pointed out in 92% Large enterprises adopt hybrid cloud strategy .Gartner Also said in a report that the future 90% Medium and large enterprises will use hybrid Cloud Architecture to manage infrastructure .
these years , With the vigorous development and implementation of cloud computing technology , More and more enterprises choose to use cloud computing technology to help them quickly complete their business digital transformation , In order to better adapt to market changes , And win more market space . A large number of enterprises are based on reducing technology development and operation and maintenance costs 、 Enjoy instant service anytime, anywhere , Choose to deploy your business in the cloud ;
There are also some enterprises due to the consideration of data sovereignty, security and privacy , Will choose to build their own proprietary cloud platform in their own internal data center environment ; For enterprise users who need both public cloud and private cloud, they will choose to build a hybrid Cloud Architecture .
Building a hybrid cloud architecture will inevitably face the problem of computer room construction , We from 《 Code for design of electronic computer room 》(GB50174-2008)B Level standards to see how to build compliance with ISO 2.0 Machine room with level III requirements .
《 Code for design of electronic computer room 》B The standard requirements of level-1 machine room are as follows :
Machine room location selection :
Distance from the parking lot | Not less than 10 rice |
Distance from railway or highway | Not less than 100 rice |
From the airport | Not less than 1600 rice |
Distance from hazardous areas in chemical plants 、 Landfill | Should not be less than 400 rice |
From the Arsenal | Should not be less than 1600 rice |
Away from the dangerous area of the nuclear power plant | Should not be less than 1600 rice |
Areas with potential for flooding | The machine room should not be set |
There may be landslide risk areas near earthquake faults | The machine room should not be set |
Areas with high crime rates | The machine room should not be set |
Environmental goals :
Temperature of main engine room ( On startup ) | 23℃±1℃ |
Relative humidity of main engine room ( On startup ) | 45%~ 55% |
Temperature of main engine room ( During shutdown ) | 5℃~35℃ |
Relative humidity of main engine room ( During shutdown ) | 40%~ 70% |
Temperature change rate of main engine room and auxiliary area ( open 、 During shutdown ) | <5℃/h |
Auxiliary zone temperature 、 Relative humidity ( On startup ) | 18~28°C、35~75% |
Auxiliary zone temperature 、 Relative humidity ( During shutdown ) | 5~35°C、20~80% |
Temperature of UPS battery room | 15~25°C |
particle concentration ( Test under static state ) | More than... Per liter of air μm The number of dust particles should be less than 18000 grain |
Architecture and structure :
Standard value of live load of main engine room (kN/m2) | 8~10 |
Main engine room hanging load (kN/m2) | |
Standard value of room live load of UPS system (kN/m2) | 8~10 |
Standard value of live load of battery room (kN/m2) | 16 |
Standard value of live load between cylinders (kN/m2) | 8 |
Daylighting windows are set on the outer wall of the main engine room | Windows should not be set |
Height of anti-static raised floor | Not less than 400mm |
Height of anti-static raised floor | Not less than 250mm |
Waterproof grade of roof | Ⅰ |
Air conditioning :
The main engine room and auxiliary area are equipped with air conditioning system | Should be |
The battery room of UPS system is equipped with air conditioning cooling system | should |
The main engine room maintains positive pressure | Should be |
Special air conditioner for machine room | N+1 redundancy Each area in the host room is redundant X platform |
The main engine room is equipped with heating radiators | Not suitable |
Electrical Technology :
Power supply | Dual power supply 、 One of the circuits shall be dedicated , Both power supplies should not be damaged at the same time |
transformer | M(1+1) redundancy (M=1、2、3······) |
Backup diesel generator system | N When the power supply cannot meet the requirements |
Basic capacity of backup diesel generator | It should include the basic capacity of the UPS system 、 Basic capacity of air conditioning and cooling equipment 、 Load capacity related to life safety, such as emergency lighting and fire fighting |
Fuel storage capacity of diesel generator | 24 Hours |
Automatic transfer switch with maintenance bypass | Automatically switch to diesel generator in case of mains failure |
UPS system configuration | N+X redundancy (X=1~N) |
Battery backup time of UPS system | 15min When the diesel generator is used as the backup power supply |
Air conditioning system power distribution | Dual power supply , End switch . Adopt radial power distribution system |
Quality requirements for power supply of electronic information equipment :
Steady state voltage fluctuation range (%) | ±3 |
Steady state frequency offset range (Hz) | ±0.5 |
Output voltage waveform distortion (%) | ≤5 |
Zero ground voltage (V) | ﹤2 |
Allowable outage duration (ms) | 0~10 |
Uninterruptible power supply system input THDI content (%) | ﹤15 |
Wiring in the machine room :
The transmission medium that undertakes information business | Optical cable or category 6 and above twisted pair cable shall be 3:1 redundancy |
Configuration of information points in the main engine room | No less than 8 It's an information point , The redundant information points are 1/4 |
Support area information point configuration | No less than 4 It's an information point |
Adopt real-time intelligent management system | can |
Public telecommunication distribution network interface | 2 individual |
Environmental and equipment monitoring system :
Air quality | particle concentration |
Air quality | temperature 、 Relative humidity 、 Differential pressure |
Water leakage detection alarm | Install water leakage sensor |
Forced drainage equipment | The running state of the equipment |
Central air conditioning and fresh air system 、 dynamic system | The running state of the equipment 、 Differential pressure of filter screen |
Special air conditioner for machine room | State parameters : switch 、 Refrigeration 、 heating 、 humidification Alarm parameters : temperature 、 Relative humidity 、 Sensor fault 、 Compressor pressure 、 Humidifier water level 、 Air volume |
Power supply and distribution system ( Power quality ) | Switch status 、 electric current 、 voltage 、 Active power 、 power factor 、 Harmonic content |
Uninterruptible power supply system | Input and output power 、 voltage 、 frequency 、 electric current 、 power factor 、 Load rate ; Battery input voltage 、 electric current 、 Capacity ; Sync / Out of sync state 、 Uninterruptible power supply system / Bypass power supply status 、 Mains failure 、 UPS system failure |
The battery | Monitor the voltage of each battery 、 Impedance and fault |
Diesel generator system | tank ( pot ) the oil level 、 Diesel engine speed 、 Output power 、 frequency 、 voltage 、 power factor |
Centralized control and management of the host | use KVM Switching systems |
Security system :
Generator room 、 Power transformation and distribution room 、 Uninterruptible power supply system room 、 Power station building | Access control ( The card reader is used as the reading device )、 Video surveillance |
The monitoring center | Access control ( The card reader is used as the reading device )、 Video surveillance |
Main engine room entrance | Access control ( The card reader is used as the reading device )、 Video surveillance |
In the main engine room | Video surveillance |
Around buildings and parking lots | Video surveillance |
water supply 、 Drainage :
Water supply and drainage pipelines unrelated to the main engine room pass through the main engine room | Should not |
The drainage system is set on the ground of the main engine room | Should be |
eliminate prevent :
The main engine room is equipped with a clean gas fire extinguishing system | should |
Main engine room 、 Power transformation and distribution 、 The uninterruptible power supply system and battery room are equipped with automatic sprinkler system | — |
Adopt inspiratory smoke detection fire alarm system | should |
Equal insurance 2.0 The specific requirements for the construction of level III machine room are as follows :
Physical location selection | The machine room and office space shall be selected in the place with shockproof facilities 、 In buildings with wind and rain resistance |
The machine room site should not be set on the top floor of the building or The basement , Otherwise, waterproof and moisture-proof measures shall be strengthened | |
Physical access control | The entrance and exit of the machine room shall be equipped with electronic access control system , control 、 Identify and record people who enter |
Prevent theft and damage | Equipment or major components shall be fixed , And set obvious marks that are not easy to remove |
The communication cable shall be laid in a concealed safe place | |
The machine room anti-theft alarm system or Set up a specially assigned video monitoring system | |
Lightning protection | All kinds of cabinets shall be installed 、 Facilities and equipment Safely grounded through the grounding system |
Measures should be taken to prevent inductive lightning , for example Set lightning protector or overvoltage protection device | |
Fire prevention | The machine room shall be equipped with automatic fire fighting system , It can detect fire automatically 、 automatic alarm , And put out the fire automatically |
Machine room and related working rooms and auxiliary rooms Building materials with fire resistance rating shall be used | |
The computer room shall be divided into areas for management , Isolation and fire prevention measures shall be set between areas | |
Water and moisture resistance | Measures shall be taken to prevent rainwater from passing through the windows of the machine room 、 Roof and wall penetrations |
Measures should be taken to prevent water vapor condensation and Transfer and infiltration of underground water | |
Detection instruments or elements sensitive to water shall be installed , Carry out waterproof detection and alarm for the machine room | |
Antistatic | Anti static floor or ground should be used and Take necessary grounding and anti-static measures |
Measures should be taken to prevent the generation of static electricity , For example, electrostatic eliminator is used 、 Wear antistatic bracelets, etc | |
Temperature and humidity control | Temperature should be set 、 Automatic humidity control facilities , The machine room is warm 、 The change of humidity is within the allowable range of equipment operation . |
Power supply | The power supply line of the machine room shall be equipped with a voltage stabilizer And overvoltage protection equipment |
Short term standby power supply shall be provided , At least meet the normal operation requirements of the equipment in case of power failure | |
Redundant or parallel The power cable line supplies power to the computer system | |
Electromagnetic protection | a) Power line and communication cable shall be laid in isolation , Avoid interfering with each other . |
b) Electromagnetic barrier shall be implemented for key equipment . |
From waiting for insurance 2.0 According to the construction requirements of level III computer room , Computer room B The level-1 standard meets the equal guarantee 2.0 Level III requirements for machine room .
References :
· Guozhun GBT22239-2019 Information security technology Basic requirements for network security level protection
· Guozhun GB50174-2008 Code for design of electronic computer room
Learn about the new titanium cloud service
Previous technical dry goods
· Ten thousand words long text : Cloud Architecture Design Principles | attach PDF download
· Ten thousand words long text | Use RBAC Restricted pair Kubernetes Access to resources
· Ten thousand words long text | oriented k8s Programming , How to write a Operator
· Terraform actual combat | Ten thousand words long text
· CephFS Performance benchmarking and cluster optimization | Ten thousand word summary
· Low code development , Development by the whole people , Eliminate professional programmers !
· Domestic mainstream public cloud VPC Use comparison and summary
· Ceph OSD Troubleshooting | Ten thousand words experience summary
· IT Hybrid cloud strategy : What is it? 、 Why? , How to build ?
Share
Poke at
边栏推荐
- The difference between redirectto and navigateto in uniapp
- Three application characteristics of immersive projection in offline display
- How engineers treat open source -- the heartfelt words of an old engineer
- Rails 4 asset pipeline vendor asset images are not precompiled
- Typescript incremental compilation
- 2022/2/11 summary
- 如何判断一个数组中的元素包含一个对象的所有属性值
- Linear algebra of deep learning
- The way of intelligent operation and maintenance application, bid farewell to the crisis of enterprise digital transformation
- uniapp中redirectTo和navigateTo的区别
猜你喜欢
深度学习之数据处理
Idea automatically imports and deletes package settings
互动滑轨屏演示能为企业展厅带来什么
Amazon MemoryDB for Redis 和 Amazon ElastiCache for Redis 的内存优化
Imeta | Chen Chengjie / Xia Rui of South China Agricultural University released a simple method of constructing Circos map by tbtools
How to set encoding in idea
Attention slam: a visual monocular slam that learns from human attention
Lombok 同时使⽤ @Data 和 @Builder 的坑,你中招没?
The difference between redirectto and navigateto in uniapp
48 page digital government smart government all in one solution
随机推荐
Quaternion attitude calculation of madgwick
Google, Baidu and Yahoo are general search engines developed by Chinese companies_ Baidu search engine URL
How to judge whether an element in an array contains all attribute values of an object
uniapp实现从本地上传头像并显示,同时将头像转化为base64格式存储在mysql数据库中
48 page digital government smart government all in one solution
工程师如何对待开源 --- 一个老工程师的肺腑之言
Encryption algorithm - password security
【vulnhub】presidential1
Core knowledge of distributed cache
Slam d'attention: un slam visuel monoculaire appris de l'attention humaine
Advanced learning of MySQL -- Fundamentals -- four characteristics of transactions
[2022 the finest in the whole network] how to test the interface test generally? Process and steps of interface test
学习光线跟踪一样的自3D表征Ego3RT
uniapp中redirectTo和navigateTo的区别
AI super clear repair resurfaces the light in Huang Jiaju's eyes, Lecun boss's "deep learning" course survival report, beautiful paintings only need one line of code, AI's latest paper | showmeai info
英雄联盟|王者|穿越火线 bgm AI配乐大赛分享
@TableId can‘t more than one in Class: “com.example.CloseContactSearcher.entity.Activity“.
After leaving a foreign company, I know what respect and compliance are
深度学习之环境配置 jupyter notebook
Linear algebra of deep learning